BS 5467 Cables  
BS 5467 Armoured Power Cables EMMU 133 Lead covered armoured Power Cables to BS 5467

BS 5467 Cables

BS 5467 Armoured Power Cables, 1900/3300V

      Single-core 1900/3300 V cables with solid aluminum conductor

Application

These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for direct burial in the ground.

Construction

Conductor

Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228.

Insulation Colour Code

XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6)
1 Core : Brown

 

3 Cores: Brown, Black, Grey

Bedding Armour Outer Sheath

PVC (Polyvinyl Chloride) Single Core: AWA (Aluminum Wire Armour) Multi Core: SWA (Steel Wire Armour) PVC(Polyvinyl Chloride)

Technical Information

Voltage rating 1900/3300V
Temperature rating
0°C to +90°C
Bending radius
1.5mm² to 16mm²: 6 x overall diameter
                          25mm² and above: 8 x overall diameter
Flame retardant
IEC60332 part 1, BS4066 part 1

Nominal Cross-sectional Area

Nominal Insulation thickness

Nominal beddingthickness

Nominal Alum Wire Armor dia.

Nominal Sheath thickness

Approx.Overall Diameter

AprroxWeight

mm²

mm

mm

mm

mm

mm

kg/km

1x50

2

0.8

1.25

1.6

19.4

600

1x70

2

0.8

1.25

1.6

20.9

710

1x95

2

0.8

1.25

1.6

22.5

810

1x120

2

1

1.6

1.7

25.2

1065

1x150

2

1

1.6

1.7

26.5

1210

1x185

2

1

1.6

1.8

28.3

1390

1x240

2

1

1.6

1.8

30.5

1630

1x300

2

1

1.6

1.9

32.8

1900