Firetox Flame Retardant Cables | |||
Firetox Flame Retardant Cables
600/1000V XLPE Insulated, LSZH Sheathed, Armoured Power Cables ((multicore)FTX400 1RZ1-R (CU/XLPE/LSZH 600/1000V Class 2)
|
Flame Retardance (Single Vertical |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE |
Reduced Fire Propagation |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Inner Sheath(optional): LSZH Compound
Armouring(optional): Galvanized Steel Wire
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH
compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation colour as per bs7671
|
with earth conductor |
without earth conductor |
2Cores |
- |
Brown,Blue |
3Cores |
Yellow/Green,Brown,Blue |
Brown,Gray,Black |
4Cores |
Yellow/Green,Brown,Gray,Black |
Brown,Gray,Black,Blue |
5Cores |
Yellow/Green,Brown,Gray,Black,Blue |
Brown,Gray,Black,Blue,Black |
above 5 Cores |
Yellow/Green,Black Numbered |
Black Numbered |
sheath colour: Black
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5s max.
Minimum bending radius: 8 x Overall Diameter (unarmoured cable)
10 x Overall Diameter (armoured cable)
CONSTRUCTION PARAMETERS
Conductor | FTX400 1RZ1-R | FTX400 1RZ1MZ1-R | ||||||
No. of |
No./ |
Nominal |
Unarmoured | Armoured | ||||
Nominal |
Approx. |
Diameter |
Armour |
Nominal |
Approx. |
|||
mm2 |
No./mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
5x1.5 |
7/0.53 |
0.7 |
11.3 |
184 |
9.9 |
0.9 |
14.5 |
402 |
7x1.5 |
7/0.53 |
0.7 |
12.4 |
225 |
11.2 |
0.9 |
16.0 |
490 |
10x1.5 |
7/0.53 |
0.7 |
15.6 |
325 |
14.3 |
1.25 |
20.0 |
761 |
12x1.5 |
7/0.53 |
0.7 |
16.2 |
370 |
14.8 |
1.25 |
20.5 |
827 |
19x1.5 |
7/0.53 |
0.7 |
19.0 |
516 |
17.4 |
1.6 |
24.0 |
1186 |
27x1.5 |
7/0.53 |
0.7 |
22.7 |
712 |
21.3 |
1.6 |
28.1 |
1537 |
37x1.5 |
7/0.53 |
0.7 |
25.5 |
941 |
23.9 |
1.6 |
30.7 |
1856 |
48x1.5 |
7/0.53 |
0.7 |
29.0 |
1186 |
27.5 |
1.6 |
34.6 |
2276 |
5x2.5 |
7/0.67 |
0.7 |
12.8 |
237 |
11.2 |
0.9 |
15.8 |
496 |
7x2.5 |
7/0.67 |
0.7 |
13.8 |
303 |
12.4 |
0.9 |
17.2 |
602 |
10x2.5 |
7/0.67 |
0.7 |
17.5 |
426 |
15.9 |
1.25 |
21.8 |
943 |
12x2.5 |
7/0.67 |
0.7 |
18.1 |
489 |
16.5 |
1.25 |
22.4 |
1020 |
19x2.5 |
7/0.67 |
0.7 |
21.3 |
725 |
19.9 |
1.6 |
26.7 |
1498 |
27x2.5 |
7/0.67 |
0.7 |
25.5 |
1004 |
23.9 |
1.6 |
30.9 |
1933 |
37x2.5 |
7/0.67 |
0.7 |
28.7 |
1334 |
26.9 |
1.6 |
33.9 |
2372 |
48x2.5 |
7/0.67 |
0.7 |
32.9 |
1706 |
31.3 |
2.0 |
39.6 |
3252 |
5x4 |
7/0.85 |
0.7 |
14.2 |
324 |
12.6 |
1.25 |
18.2 |
712 |
7x4 |
7/0.85 |
0.7 |
15.5 |
422 |
14.1 |
1.25 |
19.8 |
871 |
10x4 |
7/0.85 |
0.7 |
19.7 |
597 |
18.5 |
1.25 |
24.4 |
1213 |
12x4 |
7/0.85 |
0.7 |
20.3 |
690 |
19.1 |
1.6 |
25.7 |
1462 |
19x4 |
7/0.85 |
0.7 |
24.0 |
1037 |
22.6 |
1.6 |
29.4 |
1931 |
27x4 |
7/0.85 |
0.7 |
28.8 |
1445 |
27.2 |
1.6 |
34.4 |
2532 |
37x4 |
7/0.85 |
0.7 |
32.5 |
1932 |
31.1 |
2.0 |
39.3 |
3448 |
48x4 |
7/0.85 |
0.7 |
37.3 |
2479 |
35.7 |
2.0 |
44.2 |
4273 |
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
FTX400 1RZ1-R
Current-Carrying Capacities (Amp)
Conductor cross- sectional area |
Reference |
Reference method 3 (enclosed in conduit on |
Reference method |
Reference method 11 (on a perforated cable tray, horizontal or vertical) |
Reference method 12 (free air) |
||||||
Horizontal flat spaced |
Vertical flat spaced |
Trefoil |
|||||||||
|
2 cables, single- phase a.c. or d.c. |
3 or 4 cables, |
2 cables, single- phase a.c. or d.c |
3 or 4 cables, |
2 cables, single- phase a.c. or d.c. flat and touching |
3 or 4 cables, |
2 cables, single- phase a.c. or d.c. or flat and touching |
3 or 4 cables, |
2 cables, single- phase a.c. or d.c. |
2 |
3 cables, trefoil |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
18 |
17 |
22 |
19 |
25 |
23 |
- |
- |
- |
- |
- |
2.5 |
24 |
23 |
30 |
26 |
34 |
31 |
- |
- |
- |
- |
- |
4 |
33 |
30 |
40 |
35 |
46 |
41 |
- |
- |
- |
- |
- |
Voltage Drop (Per Amp Per Meter)
Size of conductor |
2 cables d.c. |
2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | |||||||||
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) |
Ref. Methods 1 and 11 (clipped direct or on trays touching) |
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) |
Ref. Methods 1, 11 and 12 (in trefoil) |
Ref. Methods 1 and 11(Flat and touching) |
||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
||||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
||||||
1.5 |
31 |
31 |
27 |
27 |
27 |
27 |
||||||
2.5 |
19 |
19 |
16 |
16 |
16 |
16 |
||||||
4 |
33 |
12 |
10 |
10 |
10 |
10 |
FTX400 1RZ1MZ1-R
Current-Carrying Capacities (Amp)
Conductor crosssectional area |
Reference Method 1 (clipped direct) |
Reference Method 11 (on a perforated horizontal cable trayor Reference Method 13 [free air] ) |
In single-way ducts |
Laid direct in ground |
||||
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
27 |
23 |
29 |
25 |
- |
23 |
- |
28 |
2.5 |
36 |
31 |
39 |
33 |
- |
30 |
- |
36 |
4 |
49 |
42 |
52 |
44 |
- |
40 |
- |
48 |
Voltage Drop (Per Amp Per Meter)
Conductor cross-sectional area |
2-core cable d.c. |
2 cables, single-phase a.c. |
3 or 4 cables, 3-phase a.c. |
2 cables, single- phase a.c. |
3 or 4 cables, |
In ducts or in ground |
In ducts or |
||||
1 |
2 |
3 |
4 |
5 |
6 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
1.5 |
31.0 |
31.0 |
27.0 |
31.0 |
25.0 |
2.5 |
19.0 |
19.0 |
16.0 |
19.0 |
15.0 |
4 |
12.0 |
12.0 |
10.0 |
12.0 |
9.7 |