Airport Cable | |||
Current Carrying Capacities And Voltage Drop
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Current-Carrying Capacities (Amp)
Conductor crosssectional area |
Reference Method 4 (enclosed in conduit in thermally insulating wall etc) |
Reference Method 3 (enclosed in conduit on a wall or in trunking etc) |
Reference Method 1 (clipped direct) |
Reference Method
11 (on a perforated cable tray, horizontal or vertical) |
Reference Method 12 (free air) | ||||||
Horizontal flat spaced |
Vertical flat spaced |
Trefoil | |||||||||
2 cables, single phase a.c. or d.c. |
3 or 4 cables, 3-phase a.c. |
2 cables, single phase a.c. or d.c. |
3 or 4 cables, 3-phase a.c. |
2 cables, single phase a.c. or d.c. flat and touching |
3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single -phase a.c. or d.c. or flat and touching |
3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single phase a.c. or d.c. or 3 cables three phase |
2 cables, single phase a.c. or d.c. or 3 cables three phase |
3 cables, trefoil 3-phase phase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
1.0 |
13 |
- |
- |
- |
15 |
- |
- |
- |
- |
- |
- |
1.5 |
18 |
17 |
22 |
19 |
25 |
23 |
- |
- |
- |
- |
- |
2.5 |
24 |
23 |
30 |
26 |
34 |
31 |
- |
- |
- |
- |
- |
Voltage Drop (Per Amp Per Meter)
Nominal |
2 cables |
2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | |||
Ref. Methods 3 |
Ref. Methods 1 |
Ref. Methods 3 |
Ref. Methods 1, |
Ref. Methods 1 and 11 |
||
11 and 12 (in |
(Flat and touching) |
|||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
1.0 |
46 |
46 |
- |
- |
- |
- |
1.5 |
31 |
31 |
27 |
27 |
27 |
27 |
2.5 |
19 |
19 |
16 |
16 |
16 |
16 |