High Voltage Cables

    High Voltage Cables

230/400kV XLPE Insulated, PE Sheathed High Voltage Power Cables

Application

These single core cables are designed for distribution of electrical power with nominal voltage 230/400kV. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Standard

IEC 62067

Construction

230/400kV XLPE Insulated, PE Sheathed High Voltage Power Cables
Conductor The cable conductors can be made of copper or aluminium, depending on customer’s preference or current carrying capacity. Large size solid conductors are made of aluminium. Available constructions including: round solid conductors up to 2000mm^2 (RE); circular stranded compacted conductors up to 1200mm^2 (RM); circular conductors with shaped wires up to 2000mm^2 (RM, Keystone conductors); segmental conductors up to 2500 mm^2 (RMS, Milliken conductors); oval shaped stranded compacted conductors up to 800mm^2 for external gas pressure cables (OM).
Conductor Screen Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely.
Insulation Insulation is of cross-linked polyethylene compound XLPE.
Insulaton Screen Extruded layer of semi-conducting cross-linkable compound is applied over the insulation.
Metallic Layer The metallic layer may be applied over the core assembly collectively. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.
Separation Sheath Aluminum Tape sheath.
Outer Sheath PE

Dimensional Data

Nom. Cross-Section Area Nom. Insulation Thickness Copper Wire Screen Area Approx. Overall Diameter Approx. Weight
CU AL
mm^2 mm mm^2 mm kg/m
630 33.0 170 118 17 13
800 31.0 170 118 18 13
1000(RM) 29.0 170 118 20 14
1000(RMS) 29.0 170 121 20 14
1200 27.0 170 120 22 14
1400 27.0 170 123 24 15
1600 27.0 170 127 26 16
1800 26.0 170 128 28 17
2000 26.0 170 131 30 18
2500 26.0 170 138 36 20

Electrical Data

Nom. Cross-Section Area D C Resistance @20°C A C Resistance @90°C Capacitance per core Inductance Current Ratings/PowerRatings (continuous load)
Cu conductor Al conductor
Cu Al Cu Al 1 circuit 2 circuits 1 circuit 2 circuits
mm^2 Ω/km Ω/km Ω/km Ω/km μF/km mH/km A/MVA A/MVA
trefoil installation
630 0.0283 0.0469 0.0393 0.0622 0.119 0.46 594/412 481/333 499/346 406/281
800 0.0221 0.0367 0.0317 0.0500 0.134 0.44 636/441 512/355 545/378 440/305
1000(RM) 0.0176 0.0291 0.0276 0.0409 0.150 0.41 671/465 538/373 587/407 471/326
flat installation
1000(RM) 0.0176 0.0291 0.0232 0.0375 0.156 0.56 938/650 804/557 748/518 641/444
1200 0.0151 0.0247 0.0201 0.0319 0.171 0.55 1001/694 855/592 808/560 690/478
1400 0.0129 0.0212 0.0175 0.0275 0.180 0.53 1070/741 912/632 868/601 740/513
1600 0.0113 0.0186 0.0156 0.0240 0.188 0.52 1125/779 957/663 924/640 787/545
1800 0.0101 0.0165 0.0142 0.0213 0.201 0.51 1168/809 990/686 973/674 826/572
2000 0.0090 0.0149 0.0129 0.0193 0.209 0.50 1212/840 1026/711 1016/704 861/597
2500 0.0072 0.0119 0.0109 0.0156 0.226 0.47 1289/893 1086/752 1112/770 938/650